So my delta t on the [[Mitsubishi 6kW Ecodan Heat Pump|ASHP]] is usually around the 3c. [[AI Gemini]] suggested that the pump speed was too fast, so I've bumped this down from 3 to 2. The current flow temp is 45c (for 2.5 hours), we're 1c off room temp target. Lets see if we get a change.
@ pump speed 3, 23w, 17L/min = ~3.5c
@ pump speed 2, 18w, 15L/min = 3.5 - 4c
@ pump speed 1, 13w, 13L/min = 4.5 - 5c
lol, **IGNORE THESE FIGURES**, the kitchen [[UFH|ufh]] was off!!
I thought the ufh actuators were NO, but they're NC
I suppose this info could be useful at some point